ABC, Distribution System Overhead Cable (1000V)
Product Detail
Basic Info
Extra Informatie.
Beschrijving
Description
Cables for use on urban and rural overhead distribution systems. Cables consist of phase conductors twisted around the neutral messenger made of aluminium alloy Almelec. One or more street lighting conductors may be added to the bundle. Insulation on all conductors. CROSS LINKED POLYETHYLENE (XLPE).
BUNDLE MAIN CHARACTERISTICS TO SABS 1418 – 1986
Bundle Size mm² Phase Neutral Lighting |
Bundle | Phase Conductor Approx. Ø Mm |
Neutral Conductor Approx. Ø Mm |
Lighting Conductor Approx. Ø Mm |
Max Current Rating Air at 30°C |
3 volt Drop PF=1.0 At 30°C V/A/km |
Max Liner Resistance Per phase Conductor At 30°C-km |
|
Approx Overall Ø Mm |
Approx Weight Kg/m |
|||||||
3X25 + 54.6 + 1X25 | 29 | 0.70 | 9 | 12.4 | 9 | 98 | 2.62 | 1.200 |
3X35 + 54.6 + 1X25 | 31 | 0.82 | 10.2 | 12.4 | 9 | 120 | 1.89 | 0.868 |
3X50 + 54.6 + 1X25 | 33 | 0.95 | 11.6 | 12.4 | 9 | 150 | 1.40 | 0.641 |
3X70 + 54.6 + 1X25 | 37 | 1.25 | 13.7 | 12.4 | 9 | 200 | 0.97 | 0.443 |
3X95 + 54.6 + 1X25 | 41 | 1.45 | 15.2 | 12.4 | 9 | 240 | 0.71 | 0.320 |
3X120 + 70 + 1X25 | 45 | 1.70 | 16.5 | 13.5 | 9 | 280 | 0.57 | 0.253 |
3X35 + 35BN | 23 | 0.47 | 9.65 | 7.05 | N/A | 130 | 1.08 | 0.868 |
3X70 + 50BN | 30 | 0.84 | 11.05 | 8.05 | N/A | 205 | 0.55 | 0.443 |
Cable Description |
Size (mm²) | Current Rating (AMP) |
Weight (kg/m) |
2X25 | 25 | 98 | 0.23 |
4X25 | 25 | 92 | 0.46 |
2X16AI | 16 | 80 | 0.15 |
4X16AI | 16 | 74 | 0.30 |
4 Airdac | 4-Phase & Neutral, 2.5 Earth |
50 | 0.16 |
6 Airdac | 6-Phase & Neutral, 4 Earth |
65 | 0.22 |
10 Airdac | 10-Phase & Neutral, 7.5 Earth |
90 | 0.32 |
16 Airdac | 16-Phase & Neutral, 10 Earth |
125 | 0.49 |
4 Airdac II | 4 | 50 | 0.12 |
10 Airdac II | 10 | 86 | 0.25 |
16 Airdac II | 16 | 125 | 0.41 |
We can also supply following:
———————————————————————————————-
Duplex Service Drop
AAC-Aluminum Conductor
Applications
To supply 120 volt aerial service for temporary service at construction sites, outdoor or street lighting. For service at 600 volts or lower at a conductor temperature of 75 °C maximum.
Construction
Concentric strand or compressed 1350-H19 conductor, polyethylene or cross linked polyethylene insulation, concentric strand AAC, ACSR, or 6201 alloy neutral messenger.
Standards
1. B230 aluminum wire, 1350-H19 for electrical purposes
2. B231 aluminum conductors, concentric-lay stranded
3. B232 aluminum conductors, concentric-lay-stranded, coated steel reinforced(ACSR)
4. B399 concentric-lay stranded 6201-T81 aluminum alloy conductors
5. B499 zinc-coated steel core wire for aluminum conductors, steel reinforced(ACSR)
6. Duplex service drop cable meets or exceeds all applicable requirements of ANSI/ICEA S-76-474
Item | Phase Condutor Size AWG |
Phase Conductor Strading |
Phase Conductor Insulatin Thickness |
Bare Neutral Messenger Size AWG |
Bare Neutrl Stranding |
Pekingese | 6 | Solid | 45mls | 6 | 7/w |
Collie | 6 | 7/w | 45mls | 6 | 7/w |
Dachshund | 4 | Solid | 45mls | 4 | 7/w |
Spaniel | 4 | 7/w | 45mls | 4 | 7/w |
Doberman | 2 | 7/w | 45mls | 2 | 7/w |
Malemute | 1/0 | 19/w | 60mls | 1/0 | 7/w |
- Next: ACSR, DIN Standard, 95/15mm2
- Previous: Aluminum Conductor XLPE Insulated 35mm ABC Cable (3*35+54.6+1*16, NFC standard)
Contact us
Soortgelijk of gerelateerd
-
LEIDER 3X35+1X50mm2 0.6/1kV van het ALUMINIUM van de KABEL PRE-ASSEMBLED
-
ABC de Kabel 0.6/1kV 1X25+25mm2 XLPE isoleerde Pre-assembled Leiders
-
ABC Kabel van het Lage Voltage 0.6/1kV van de Kabel 3X95mm2+1X70mm2 de Lucht Gebundelde
-
0.6/1kV 3X35+1X54,6mm2 Verdraaide ABC Lucht Gebundelde LuchtKabel N-F C 33-209