ABC kabel Triplex Service Drop AAC/XLPE+ACSR Janthina
Basic Info
CE ,
UL ,
CCC ,
RoHS ,
VDE
Extra Informatie.
Beschrijving
1 Type:Duplex Service Drop, Triplex Service Drop, Quadruplex Service Drop
Duplex Service Drop
Applications:To supply 120 volt aerial service for temporary service at construction sites,outdoor or street lighting . For service at 600 volts or lower at a conductor temperature of 75 maximum.
Triplex Service Drop
Applications: To supply power from the ulility`s lines to the consumer`s weatherhead. For service at 600 volts or less(phase to phase ) at a conductor temperature of 75 maximum for PE insulation or 90 maximum for XLPE insulation .
Service Drop
Applications: Used to supply 3 phase power , usually from a pole-mounted transformer to the use`s servic head where connection to the service entance cable is made . To be used at voltages of 600 volts or less phase to phase and at conductor temperature not to exceed 75 for PE insulated conductors or 90 for XLPE insulated conductors.
2 Construction
a Phase Conductor construction:The phase conductor is aluminum alloy 1350-H19 hard-drawn, compressed concentric-lay-stranded.
b Neutral Conductor Construction
Cable assemblies are available with the following neutral conductors:
Aluminum conductors, coated-steel reinforced (ACSR), concentric-lay-stranded
Aluminum alloy 1350-H19 hard-drawn, concentric-lay-stranded
Aluminum alloy 6201-T81, concentric-lay-stranded
c Insulation Material
The standard insulation on the phase conductor is black low-density crosslinked polyethylene (XLPE)
Alternatively, black linear low-density polyethylene (LLDPE) insulation with a 75°C temperature rating is available upon request.
3 specification
see following table
4.Standards
1. B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
2. B-231 Aluminum Conductors, Concentric-Lay-Stranded.
3. B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
4. B-399 Concentric-Lay_Stranded 6201-T81 Aluminum Alloy Conductors.
5. B498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
6. Duplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA S-76
Duplex Service Drop
Code word |
AWG or kcmil | Bare Neutral Messenger | Phase conductor | Weight Kg/km |
Allowcable Ampacities(A) |
|||||||
ACSR | Rated Strength Lbs. |
AAC | Insul Thick.mm |
XLPE | PE | |||||||
Number | Dia. mm |
Number | Dia.mm | Number | Dia.mm | |||||||
Setter Shepherd Eskimo Terrier Chow Bull |
1*6AWG+1*6AWG 1*6AWG+1*6AWG 1*4AWG+1*4AWG 1*4AWG+1*4AWG 1*2AWG+1*2AWG 1*1/0AWG+1*1/0AWG |
1 1 1 1 1 1 |
1.68 1.68 2.12 2.12 2.67 3.37 |
6 6 6 6 6 6 |
1.68 1.68 2.12 2.12 2.67 3.37 |
1190 1190 1860 1860 2850 4380 |
1 7 1 7 7 19 |
4.11 1.56 5.19 1.96 2.47 1.89 |
1.14 1.14 1.14 1.14 1.14 1.52 |
111 113 171 173 266 427 |
85 85 115 115 150 205 |
70 70 90 90 120 160 |
Triplex ABC Cable
Code*Word | Phase conductor | Bare Neutral Message | Nominal lay Length | Weight Per 1000 ft.(lbs.) | Allo wable Amp acitles | ||||||
Size (A WG) | Stranding | Insul Thick(Mils) | Size (AWG) | Stranding | Rated Strength (lbs.) | inches | XLP | POLY | XLP | POLY | |
AAC Neutral-messenger | |||||||||||
Pateela | 6 | 7 | 45 | 6 | 7 | 563 | 14.88 | 103 | 103 | 85 | 70 |
Oyster | 4 | 7 | 45 | 4 | 7 | 881 | 14.88 | 154 | 154 | 115 | 90 |
Clam | 2 | 7 | 45 | 2 | 7 | 1350 | 20.58 | 233 | 233 | 150 | 120 |
Murex | 1/0 | 7 | 60 | 1/0 | 7 | 1990 | 20.58 | 374 | 374 | 205 | 160 |
Purpura | 1/0 | 9 | 60 | 1/0 | 7 | 1990 | 20.58 | 368 | 368 | 205 | 160 |
Nassa | 2/0 | 7 | 60 | 2/0 | 7 | 2510 | 25.42 | 462 | 462 | 235 | 185 |
Melita | 3/0 | 17 | 60 | 3/0 | 19 | 3310 | 29.97 | 562 | 562 | 275 | 215 |
Portunus | 4/0 | 18 | 60 | 4/0 | 19 | 4020 | 29.97 | 696 | 696 | 315 | 245 |
Nannynose | 336.4 | 19 | 60 | 336.4 | 19 | 6146 | 38.79 | 1118 | 1118 | 420 | 325 |
*Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Chihuahua/XLP) +Conductor temperature of 90 for XLP,75 for Poly;ambient temperature of 40;emissivity 0.2;2ft./sec.Wind in sun. |
QuadruplexABC Cable
Code*Word | Phase conductor | Bare Neutral Message | Nominal lay Length | Weight Per 1000 ft.(lbs.) | Allo wable Amp acitles | ||||||
Size (A WG) | Stranding | Insul Thick(Mils) | Size (AWG) | Stranding | Rated Strength (lbs.) | inches | XLP | POLY | XLP | POLY | |
AAC Neutral-messenger | |||||||||||
Clydessdale | 4 | 1 | 45 | 4 | 7 | 881 | 20.58 | 198 | 198 | 100 | 80 |
Pinto | 4 | 7 | 45 | 4 | 7 | 881 | 20.58 | 211 | 211 | 100 | 80 |
Mustang | 2 | 7 | 45 | 2 | 7 | 1350 | 25.42 | 318 | 318 | 135 | 105 |
Criollo | 1/0 | 9 | 60 | 1/0 | 7 | 1990 | 25.42 | 503 | 503 | 180 | 140 |
Percheron | 2/0 | 11 | 60 | 2/0 | 7 | 2510 | 29.97 | 619 | 619 | 205 | 160 |
Hanovarian | 3/0 | 17 | 60 | 3/0 | 19 | 3310 | 35.18 | 764 | 764 | 235 | 185 |
Oldenburg | 4/0 | 18 | 60 | 4/0 | 19 | 4020 | 35.18 | 945 | 945 | 275 | 210 |
Lippizaner | 336.4 | 19 | 80 | 336.4 | 19 | 6146 | 38.79 | 1519 | 1519 | 370 | 280 |
*Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Chihuahua/XLP) +Conductor temperature of 90 for XLP,75 for Poly;ambient temperature of 40;emissivity 0.2;2ft./sec. |