De middelgrote Kabel van de Macht van de Draad van het Staal van het Voltage XLPE Geïsoleerde Gepantserde

 De middelgrote Kabel van de Macht van de Draad van het Staal van het Voltage XLPE Geïsoleerde Gepantserde

Product Detail

Basic Info

Model No:YJV32
Toepassing: Bouw , Boven het hoofd , Ondergronds , Industrieel , Centrale
Voltage: Laag-en middenspanning Kabel
Isolatiemateriaal: XLPE
Certificaat: ISO , CCC , CE , RoHS , UL , VDE

Extra Informatie.

Handelsmerk:yifangcable
Verpakking:Drum, Reel or According to Customers' Request
Standaard:IEC, BS, DIN, ASTM, JIS, GOST, etc
Oorsprong:Zhengzhou, Henan, China
Gs-Code:8544601200
Productiecapaciteit:500

Beschrijving

Payment & Shipping Terms:
Packaging Details: Wooden and steel drum
Payment Terms: L/C, T/T
Supply Ability: 100 Kilogram per Month

1. The products are mainly complying with iec 60502 standard, also can be produced according to OEM requirements and other standards, such as bs standard, DIN standard, ASTM standard, etc.

Voltage grade is up to 35kv, cross-section area can be up to 400 sqmm (copper or aluminiun conductor). Conductor long-time operating temperature is 90 degrees. In short circuit, conductor highest temperature should be not more than 250 degrees.

2. Brief Construction:
Single core or multi-core
Copper or aluminium conductor
XLPE insulation
Copper tape or copper wire screen
Galvanized steel tape armored
PVC or PE sheath

3. Laying conditions: For laying under ground with large different altitude, be able to bear external machanical force and moderate pulling force

4. We can design and manufacture special XLPE cable according to other standards required by customers.

2. Application and Main type

Type Description Main Apllication
Copper Conductor Aluminum Conductor
YJV
Cu/XLPE/PVC
YJLV
Al/XLPE/PVC
Copper or aluminum conductor
XLPE insulated, Copper tape
screen PVC shealthed power cable
For laying indoor, tunnel, underground and cannel.
Unable to bear external mechanical pulling force and pressure during laid.
YJV
Cu/XLPE/L(H)DPE
YJLV
Al/XLPE/L(H)DPE
Copper or aluminum conductor 
XLPE insulated, Copper tape screen
PE/LDPE/HDPE shealthed power cable
YJE
Cu/XLPE/LSOH
YJLE
Al/XLPE/LSOH
Copper or aluminum conductor XLPE
insulated, Copper tape
screen LSOH shealthed power cable
YJSV
Cu/XLPE/CWS/PVC
N2XS(SE)Y
YJLSV
Al/XLPE/CWS/PVC
N2XS(SE)Y
Copper or aluminum conductor XLPE
insulated, Copper wire+Coper tape
screen PVC shealthed power cable
   
For laying indoor, tunnel, underground and cannel.
Unable to bear external mechanical pulling force and pressure during laid, fault current requires large.
CWS(Copper wire screen)
type:A: Fixed section 
B: Full/one third/one sixth/one eighth/one sixteenth neutral
YJSY
Cu/XLPE/CWS/L(M.H)DPE
N2XS(SE)2Y
 
YJLSY
Al/XLPE/CWS/L(M.H)DPE
N2XS(SE)2Y
Copper or aluminum conductor XLPE
insulated, Copper wire+Coper tape
screen PE/LDPE/HDPE shealthed power cable
 YJE
Cu/XLPE/CWS/LSOH
YJLE
Al/XLPE/CWS/LSOH
Copper or aluminum conductor XLPE
Copper wire+Coper tape
screen LSOH shealthed power cable
YJV22
Cu/XLPE/STA/PVC
YJLV22
 Al/XLPE/STA/PVC
Copper or aluminum conductor XLPE
insulated, Copper tape screen, steel tape armoured, PVC sheathed power cable
   
For laying indoor, tunnel, underground and cannel.
Able to bear external mechanical forces, but unable to bear large pulling force.
 YJV23
 Cu/XLPE/STA/L(M.H)PE
YJLV23
Al/XLPE/STA/L(M.H)PE
Copper or aluminum conductor XLPE
insulated, Copper tape screen, steel tape armoured, PE/LDPE/HDPE sheathed power cable
 WD-YJY23
Cu/XLPE/STA/LSOH
WD-YJLY23
Al/XLPE/STA/LSOH
Copper or aluminum conductor XLPE insulated, Copper tape screen, steel tape armoured, PVC sheathed power cable
 
 YJSV22
Cu/XLPE/CWS/STA/PVC
N2XSEBY
YJLSV22
Al/XLPE/CWS/STA/PVC
N2XSEBY 
Copper or aluminum conductor XLPE insulated,
Copper wire+Coper tape screen,steel tape armoured, PVC shealthed power cable
 
For laying indoor, tunnel, underground and cannel.
Able to bear external mechanical forces, but unable to bear large pulling force. fault current requires large.
CWS(Copper wire screen)
type:A: Fixed section 

3. Scope of voltge grade and core number and cross-section
   a) National standard

Rated voltage(kv) 3.6/6 6/6 6/10 8.7/10 8.7/15 12/15 12/20 18/20 18/30 21/35 26/35
Core Number 1 core, 3 core
Cross-section
mm2
1C 25~800 35~800
3C 25~400 35~400

  b) IEC/BS/DIN standard

Rated voltage(kv) 3.6/6 6/6 6/10 8.7/10 8.7/15 12/15 12/20 18/20 18/30 21/35 26/35
Core Number 1 core, 3 core
Cross-section
mm2
1C 25~800 35~800
3C 25~400 35~400

 
  c) ASTM standard

Rated voltage(kv) 5001-8000 8001-15000 15001-25000 25001-28000 28001-35000 35001-46000
  1 core, 3 core
Cross-section
mm2
1C
 
6AWG~1600kcmil 2AWG~1600kcmil 1AWG~1600kcmil 2AWG~1600kcmil 1/0AWG~1600kcmil
 
3C
    1AWG~1600kcmil 2AWG~1600kcmil 4/0AWG~1600kcmil
 

 
4. D.C Resistance of finished cable at 20oC per km is not more than following:
 

Nominal Cross-section
mm2
25 35 50 70 95 120 150 185 240 300
20oC DC Resistance
Ω/km
Cu 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601
Al 1.2 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100
Nominal Cross-section
mm2
400 500 630 800 1000 1200 1400 1600 1800 2000
20oC DC Resistance
Ω/km
Cu 0.0470 0.0366 0.0283 0.0221 0.0176 0.0151 0.0123 0.0108 0.0096 0.0086
Al 0.0778 0.0605 0.0469 0.0367 0.0291 0.0247 0.0202 0.0177 0.0157  
Nominal Cross-section
AWG
6 5 4 3 2 1 1/0 2/0 3/0 4/0
20oC DC Resistance
Ω/km
Cu 1.3219 1.0453 0.8298 0.6594 0.5211 0.4149 0.3281 0.2605 0.2065 0.1640
Al 2.1699 1.7167 1.3631 1.0802 0.8551 0.6783 0.5401 0.4276 0.3376 0.2688
Nominal Cross-section
MCM
250 300 350 400 450 500 550 600 650 700
20oC DC Resistance
Ω/km
Cu 0.1386 0.1158 0.0991 0.0865 0.0772 0.0695 0.0630 0.0579 0.0534 0.0495
Al 0.2273 0.1897 0.1623 0.1421 0.1263 0.1138 0.1032 0.0948 0.0874 0.0813
Nominal Cross-section
MCM
750 800 900 1000 1100 1200 1300 1400 1500 1600
20oC DC Resistance
Ω/km
Cu 0.0463 0.0434 0.0386 0.0347 0.0316 0.0289 0.0237 0.0248 0.0231 0.0217
Al 0.0759 0.0711 0.0630 0.0569 0.0518 0.0473 0.0437 0.0405 0.0379 0.0357
 

Tags: , ,

Contact us

 

 

 

Success! Thanks for Your Request.
Error! Please Try Again.