Mv-90, Power Cable, 8 Kv, 3/C, Cu/XLPE/Cts/PVC (ICEA S-93-639/NEMA WC71/UL 1072)

 Mv-90, Power Cable, 8 Kv, 3/C, Cu/XLPE/Cts/PVC (ICEA S-93-639/NEMA WC71/UL 1072)

Product Detail

Basic Info

Model No:MV-90
Toepassing: Bouw , Ondergronds , Industrieel , Centrale
Voltage: Laag-en middenspanning Kabel
Stroom: DC-kabel
Isolatiemateriaal: XLPE
Schede Materiaal: PVC
Materiaal Vorm: Ronde Wire
Wire Core Material: Bare koperdraad
Certificaat: ISO , CCC

Extra Informatie.

Handelsmerk:DingAn
Verpakking:Heated Steel-Wooden Drum/Steel Drum
Standaard:SGS
Oorsprong:Jiangsu Yixing, China
Gs-Code:8544601200
Productiecapaciteit:12000 Km/Year

Beschrijving

MV-90, Power Cable, 8 KV, 3/C, Cu/XLPE/CTS/PVC (ICEA S-93-639/NEMA WC71/UL 1072)

Features

UL Listed as MV-90. Rated as Sunlight Resistance for CT use, 1/0 AWG and larger. Oil Resistance I jacket. True Triple extrusion system and closed handling raw materials system, to eliminate any contact with ambient, until extrusion process ends.

Application

Primary power and distribution circuits in industrial and commercial installations, power circuits in generating plants where line to ground fault current are within shield capabilities. May be used in wet or dry locations, installed in raceways, duct, and open air, aerially or directly buried where permitted by NEC.

Standards

UL 1072: Medium Voltage Power Cables.
ICEA S-93-639/NEMA WC74: 5 kV – 46 kV Shielded Power Cables.
ICEA S-97-682: Standard for Utility Shielded Power Cables Rated 5 kV- 46 kV.
AEIC CS8: Specification for Extruded Dielectric, Shielded Power Cables Rated 5 kV – 46 kV.

Specifications

Maximum operating voltage: 5 kV to 35 kV 100% and 133% IL
Maximum conductor operation temperatures:
Wet and dry locations: Normal: 90 °C, Emergency: 130 °C, Short Circuit: 250 °C

Engineering Information
1. Conductor: Soft annealed uncoated copper compacted Class B per ASTM B496 or hard drawn Aluminum-1350 compacted Class B per ASTM B400.
2. Conductor Shield: Semi conducting cross-linked polyethylene (XLPE).
3. Insulation: Thermoset crosslinked polyethylene (XLPE).
4. Insulation Shield: Semi conducting cross-linked polyethylene (XLPE).
5. Metallic Shield: Soft annealed uncoated copper tape, 5 mil thick, 25% minimum overlap.
6. Assembly: Conductors cabled with non-hygroscopic fillers, as required and binder tape.
7. Jacket: Black sunlight resistance and flame retardant thermoplastic polyvinyl chloride (PVC) compound.

100% Insulation Levels (115 mil) 133% Insulation Levels (140 mil)
Size Number of Strands Conductor Nominal Jacket Thickness Approximate Outside Diameter Approximate Net Weight Jacket Thickness Approximate Outside Diameter Approximate Net Weight
Copper Aluminum Copper Aluminum
AWG of kcmil in mil in lb/kft mil in lb/kft
6 7 0.17 80 1.34 1007 832 80 1.45 1112 938
4 7 0.21 80 1.43 1230 953 80 1.55 1341 1064
2 7 0.27 80 1.55 1562 1122 80 1.67 1680 1240
1 19 0.30 80 1.62 1820 1264 110 1.80 2053 1498
1/0 19 0.34 110 1.76 2204 1502 110 1.88 2338 1636
2/0 19 0.38 110 1.85 2575 1691 110 1.96 2714 1830
3/0 19 0.42 110 1.95 3000 1885 110 2.06 3145 2030
4/0 19 0.48 110 2.06 3524 2119 110 2.18 3675 2271
250 37 0.52 110 2.19 4004 2343 110 2.30 4163 2502
300 37 0.57 110 2.29 4619 2627 110 2.40 4784 2793
350 37 0.62 110 2.39 5198 2872 110 2.50 5369 3043
400 37 0.66 110 2.48 5765 3110 110 2.65 6034 3378
500 37 0.74 140 2.76 7200 3880 140 2.88 7397 4077
600 61 0.81 140 2.95 8313 4326 140 3.07 8521 4535
750 61 0.91 140 3.16 10022 5045 140 3.27 10243 5266
1000 61 1.06 140 3.49 12770 6136 140 3.60 13011 6376

Tags: , , , , ,