Exvb, de Kabel van de Macht, 0.6/1 Kv, Cu/XLPE/PVC (HD 603.5A)
Product Detail
Basic Info
Extra Informatie.
Beschrijving
EXVB, Power Cable, 0.6/1 Kv, Cu/XLPE/PVC (HD 603.5A)
Underground cable with XLPE insulation and PVC sheath
DESIGN
1 | Copper conductor, round solid (RE), round stranded (RM), resp. sector-shaped stranded (SM)
2 | Core insulation (XLPE)
3 | Inner covering (EPDM or plastic tape)
4 | Sheath (PVC black, UV-resistant)
Standard: HD 603.5A
Application
Power distribution cables in power stations, industrial installations and switchgears. For fi xed installation underground, in interior premises, cable ducts, in the open air, in the ground or concrete, in water – as permitted by the local building regulations – if no risk of any mechanical damage is to be expected.
Properties
Rated voltage: 0,6/1 kV
Test voltage: 3 kV/50 Hz
Max. conductor temperature: +90 °C
Max. short-circuit temperature: +250 °
Temperature range for handling: -30 up to +90 °C
Min. temperature for laying and manipulation: -5 °C
Core identifi cation: HD 308 S2
Fire properties: flame retardant: EN 60332-1-2
Number of cores x nominal cross section | Max. conductor resistance | Current rating in the ground | Current rating in the air | Outer diameter | Total weight |
(mm²) | (Ω/km) | (A) | (A) | (mm) | (kg/km) |
E-XAYY | |||||
4 x 10 RE | 1.830 | 86 | 74 | 18.8 | 730 |
4 x 16 RM | 1.150 | 112 | 98 | 21.9 | 1040 |
4 x 25 RM | 0.727 | 145 | 133 | 26.9 | 1580 |
4 x 35 RM | 0.524 | 174 | 162 | 28.8 | 1980 |
4 x 50 RM | 0.387 | 206 | 197 | 32.9 | 2,630 |
4 x 70 SM | 0.268 | 254 | 250 | 37.2 | 3,250 |
4 x 95 SM | 0.193 | 305 | 308 | 41 | 4,250 |
- Next: Cu/PVC/PVC, Control Cable, 0.6/1 Kv (IEC 60502-1)