Kabel van de Macht van de Isolatie van pvc van de Leider van Cu /Al de niet Gepantserde

 Kabel van de Macht van de Isolatie van pvc van de Leider van Cu /Al de niet Gepantserde

Product Detail

Basic Info

Model No:VV 4×240+120mm2
Toepassing: Bouw , Boven het hoofd , Centrale
Voltage: Laag-en middenspanning Kabel
Stroom: AC Cable
Isolatiemateriaal: PVC
Schede Materiaal: PVC
Materiaal Vorm: Ronde Wire
Wire Core Material: Rode Draad van het Koper
Certificaat: ISO , CCC

Extra Informatie.

Handelsmerk:JYTOP
Verpakking:Packed in Reels
Standaard:25mm2, 35mm2, 50mm2, 70mm2, 95mm2, 120mm2, 150mm2,
Oorsprong:Zhengzhou, China
Gs-Code:8544492100
Productiecapaciteit:3000 Tons / Month

Beschrijving

Cu /Al Conductor PVC Insulation Non Armoured Power Cable

A. Standard

It is manufactured under IEC 60502 standard.

B.Using Features

1.Rated voltage includes 0.6/1kv,1.8/3kv,3.6/6kv,6/6kv,6/10kv,8.7/10kv,8.7/15kv,12/20kv,18/30kv.

2.The highest allowed operating temperature of conductor for long-term working is 90°C. In short-Circuit (Max. long term is no more than 5 seconds),the highest temperature for conductor is no more than 250°C.

3. D.C Resistance of the conductor complies with the stipulations of IEC 60502.

4.The installing environment temperature should be no lower than 0°C. Otherwise it should be preheated. The Min. bending radius should be no smaller than 15 times of cable outer diameter.

5. The cable is laid without horizontal drop limit.

6. Working Frequency Voltage Test:

For cable of 3.6kv or lower:2.5 times of the Rated voltage 5 minutes without puncture

For cable of 3.6kv-18kv:3.5 times of the rated voltage 5 minutes without puncture

For cable of 20kv-30kv:2.5 times of the rated voltage 30minutes without puncture

7.Partial Discharge Test:

The discharge volume should be no more than 10pc under 1.73 times of rated voltage for cable.

8. Flame retardant cable could endure firing test in bundle stipulated IEC 60331.
 

  non armoured cable  

1, Conductor: Al wire stranded or compacted

2, Insulation: High dentisy XLPE insulation

3, Armoured: steel wire armoured, or stainless steel wire armoured, Aluminum wire armoured for single core.

4, Sheath: PVC,PE,LSOH material is available, with exellent UV resistance if use PE or LSOH material.

 

PERFORMANCE:

XLPE insulated power cable, either chemical method or physical method is employed to transform the molecular structure of PE from chain into three-dimensional network, i.e. thermo-plastc PE is transformed into thermosetting XLPE, After cross-linking, the thermal and mechanical properties of PE have been greatly improved while its exellent electrical property are still retained.

 

The mechanical and electrical properties of these cables are accordant with GB/T12706-2002 Power cables extruded insulation and their accessories of elated voltages 1kV(Um=1.2kV)up to 35kV(Um=40.5kV) and IEC60502-1997 Extruded insulation power cables and appendices for rated voltages 1kV up to 30kV

Type
  Description
Cu Al  
YJV YJLV XLPE insulation PVC sheath power cable
YJY YJLY XLPE insulation PE sheath power cable
YJV22 YJLV22 XLPE insulation, steel tape armor,  PVC sheath power cable
YJV23 YJLV23 XLPE insulation, steel tape armor,  PE sheath power cable
YJV62 YJLV62 XLPE insulation, have no the magnetism steel tape armor,  PE sheath power cable
YJV32 YJLV32 XLPE insulation, thin steel-wire  armor,  PVC sheath power cable
YJV72 YJLV72 XLPE insulation, have no the magnetism thick steel-wire  armor,  PVC sheath power cable
YJV42 YJLV42 XLPE insulation, thick steel-wire  armor,  PVC sheath power cable

 

 TECHNICAL DATA:

U0/Um(kv)
1st class 0.6/1kv 1.8/3kv 3.6/6kv 6/10kv 8.7/15kv 12/20kv 18/30kv 21/35kv
No.of Core
1 Core Section 1.5-800 25-800 25-800 25-800 35-800 50-800 50-800 50-800
 
area(mm2)
2 Core Section 1.5-185 / / / / / / /
 
Area(mm2)
3 Core 1.5-400 25-400 25-400 25-400 35-400 50-400 50-400 50-400
4 Core Section 2.5-400 25-400 / / / / / /
Area(mm2)

 

Four cores:

cross section mm2 insulated thickness mm sheath thickness mm outer diameter mm testing voltage kv current loading capacity
in the air to be laid underground
1.5 0.7 1.5 10.6 3.5 21 25
2.5 0.7 1.5 11.5 3.5 28 33
4 0.7 1.5 12.8 3.5 37 44
6 0.7 1.5 14 3.5 46 54
10 0.7 1.5 15.9 3.5 63 73
16 0.7 2 19.1 3.5 84 94
25 0.9 2 22.7 3.5 109 120
35 0.9 2 25.4 3.5 132 144
50 1 2 29 3.5 159 169
70 1.1 2 32.9 3.5 195 205
95 1.1 2.5 37.7 3.5 237 245
120 1.2 2.5 41.6 3.5 273 278
150 1.4 3 47.6 3.5 310 309
185 1.6 3 50.6 3.5 355 347
240 1.7 3 56.4 3.5 416 399
300 1.8 3.5 62.2 3.5 473 446
400 2 3.5 68.9 3.5 512 431

3+1 cores:

cross section mm2 insulated thickness mm sheath thickness mm outer diameter mm testing voltage kv current loading capacity
in the air to be laid underground
1.5 0.7 1.5 10.6 3.5 21    25
2.5 0.7 1.5 11.5 3.5 28 33
4 0.7 1.5 12.5 3.5 37 44
6 0.7 1.5 13.7 3.5 46 54
10 0.7 1.5 15.4 3.5 63 73
16 0.7 2 17.5 3.5 84 94
25 0.9 2 21.8 3.5 109 120
35 0.9 2 23.8 3.5 132 144
50 1 2 27.4 3.5 159 169
70 1.1 2 31 3.5 195 205
95 1.1 2.5 34.8 3.5 237 245
120 1.2 2.5 39.7 3.5 273 278
150 1.4 3 42.9 3.5 310 309
185 1.6 3 52.7 3.5 355 347
240 1.7 3 58 3.5 416 399
300 1.8 3.5 62.2 3.5 473 446
400 2 3.5 68.9 3.5 512 431

 

Tags: , ,